CAPDIS-M mit Modbus
Voltage transformer replacement for capacitive interfaces according to VDE 0682 T 415 or IEC 61243-5
Part-No.: 2500770
CAPDIS-M: Voltage monitoring module, pluggable to the U0 interface of a CAPDIS-Sx+
- Calibration per phase by teach function
- Voltage measurement 3-phase (switchable)
- Under- and overvoltage monitoring
- Under- and overfrequency monitoring
- Interface to voltage converter or amplifier CAPDIS-4
Technical Data
Function | Measurement, display and threshold monitoring of voltage and frequency |
Auxiliary power supply | From CAPDIS-S2+(R3), via system cable from the CAPDIS-4 or PCMC (each 24 ... 230 V AC/DC) |
Measurement | Three-phase, displayed phase selectable via button |
Accuracy CAPDIS-M/4 | <= 3% v. M.-B. after matching by teach function |
Calibration | Using teach function |
Message | Threshold exceedance via LEDs of the CAPDIS-M and relays of the CAPDIS-4 or CAPDIS-S2+(R3) |
Output | RS 485 for connection CAPDIS-4 or IKI-EDI-W, interface to CAPDIS-S2+(R3) |
Under-/ Overvoltage Function | Threshold values adjustable in increments of 1% |
Under-/ Overfrequency function | Threshold values adjustable in increments of 0.1 Hz |
Switching delays | Adjustable 0 ... 99 s |
Housing | Insert housing for CAPDIS-Sx+/PI-RR3; h x w x t = 50 x 115 x 30 mm |
Part-No. | 2500785 (default), 2500770 (with Modbus output, no connection to CAPDIS-4 possible) |