IKI-Overhead Butler
Fault indicators for overhead lines,
on-site display via LEDs,
close-range radio for querying up to 8 IKI overhead radio
Part-No.: 2501306
Error detection of all typical overhead line faults
- Short circuits, transients and earth defects
Ultra bright LED indicator
- Visibility cone 360°, visible even in bright sunlight
Easy installation by means of actuating rod
- The built-in torque indicator indicates the correct installation. No additional tools required.
Reliable fault detection
- By independent current/time characteristic (UMZ); Short circuit and earth fault detection; Detection of high-impedance errors by dI/dT/dT capture; Inrush suppression; Fault confirmation by monitoring for shutdown via integrated voltage sensor
Simple setting of parameters by DIP switches
- Response current (automatic or fixed thresholds 200 - 600 A).
- Reset time (2 - 8 h, manually or automatically after load current return). Access to DIP switches without tools possible.
Long service life
- Through high-quality lithium battery, nanowatt technology and corrosion-free housing.
Technical Data
Power supply: | Lithium battery (life of at least 10 years) |
Response current I>>: | |
Absolute response value: | automatic, 200, 400, 600 A |
dI/dT response value: | automatic, 20 A, 100 A, 200 A per 50 ms |
Response time t>>: | 80 ms, 150 ms |
Reset: | 2 h, 4 h, 8 h, manual, automatic after load current return of at least 3 A for at least 10 s |
Visibility: | approx. 50-100 m in bright sunlight; approx. 500 m at night |
Luminous intensity signal: | 13 Candela |
Flash frequency signal: | 30 per minute |
Total display time: | 2880 hours (120 days) |
Dimensions: | h = 210 mm; Ø = 130 mm |
Installation: | with actuating rod (bayonet or shotgun) |
Self-test: | with actuating rod and magnet |
IP protection class: | IP 67 |
Un: | 1 kV to 36 kV |
fn: | 50 - 60 Hz |
Operating temperature: | -30 ° C to +75 ° C |
Storage temperature: | -30 ° C to +80 ° C |
Max. wind strength: | 70 m/s |
Maximum height Operation: | 4500 m above N.N. |
Conductor cross section: | 20 mm2 up to 490 mm2 |
corresponding diameter: | 5 mm to 35 mm |
Maximum short-circuit current housing: | 25 kA < 300 s |