This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Google Analytics
Track device being used

IKI-Overhead-Radio R2
Fault indicator for the overhead line, remote message via short-range radio to Butler
Item number: 2501304
Item number: 2501304
Properties With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus... more
Product information "IKI-Overhead-Radio R2"
Properties
With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus integrated into the overall protection concept to minimize downtime. Fault indication is provided locally via strong LEDs and optionally via remote transmission to a central control station.Fault detection of all typical overhead line faults
Short circuits, transients and ground faultsUltra-bright LED display
Visibility cone 360° , visible even in bright sunlightEasy installation using actuating rod
Integrated torque indicator shows correct installation. No additional tools required.Reliable fault detection
due to independent current/time characteristic [UMZ); short and earth [short] circuit detection; high impedance fault detection by dI/dT detection; inrush suppression; fault confirmation by monitoring for disconnection via integrated voltage sensorSimple parameter setting by DIP switch
Response current (automatic or fixed thresholds 200 - 600 A). Reset time (2 - 8 h, manual or automatic after load current recovery). Access to DIP switches possible without tools.Long life
due to high quality lithium battery, nanowatt technology and corrosion-free housing.Easy installation
Torque indicator for safe mounting.
IKI overhead with remote signalling: Radio and Butler versions
All communication elements are directly installed in the overhead line indicators. Therefore, no additional remote control unit mounted on the pole is required. Easy connection to the control center via IEC 60870-5-104
With the optionally available SMS gateway, all installed IKI overhead are connected to the control center or the PONLINE system and integratedDetection of conductor breakage in the overhead line
Detection of conductor breakage without fault currentTransmission of load current values
Instantaneous or average values are transmitted cyclicallyRemote parameterization of settings possible
Communication principle
Up to 8 IKI overhead radios communicate with one IKI overhead butler via short-range radio. The IKI overhead butler communicates via GSM with the PONLINE master server or any SMS receivers. The PONLINE master server can be connected to the control room via an IEC 60870-5-104 interface.Principle of fault detection with remote signalling
The faults are detected and reported in each case up to the fault locationDisplay of all relevant status information
In conjunction with PONLINE®, all important information (faults and load flow) from the overhead line network, such as all types of faults as well as load flow information, is recorded and transmittedDevice data | |
Article number | 2501304 |
Product designation | IKI-Overhead-R2 Radio Fault Indicator for Overhead Line | Remote Message via Short Range Radio to Butler |
Display | |
Display Visibility | Approx. 50-100 m in bright sunlight approx. 500 m at night |
Display flashing frequency | 30 per minute |
Brightness display | 13 Candela |
Dimensions and installation instructions | |
Case height x width x depth | 250 x 104 x 145 mm |
Conductor cross section | 20 - 490 mm²; 5 - 35 mm diameter |
Operating conditions | |
Operating temperature | -30°C ... 75°C |
Storage temperature | -30°C ... 80°C |
Protection class | IP67 |
Voltage level | Applicable up to 36 kV |
Maximum height operation | 4500 m above sea level |
Maximum wind force | 70 m/s |
Fault detection | |
Short circuit detection I>> | ✓ |
Threshold current short-circuit detection I>> [A] | 200, 400, 600 |
Automatic response threshold Short circuit detection | ✓ |
Threshold time short-circuit detection I>> [ms] | 80, 150 |
Threshold time short-circuit detection (I>>) adjustable via DIP [ms] | 80, 150 |
Waiting time after current switch-off (short-circuit detection) [ms] | 200 |
Earth short-circuit detection Ie>> | ✓ |
Reset setting | 2, 4, 8 h |
Reset | Time, manually by actuating rod, automatically after load current return > 3 A |
Communication | |
Frequency bands | 4 |
Remote signalling | Short distance radio to IKI overhead butler |
Power supply | |
Battery | Lithium battery |
Battery life | Min. 10 years |
Battery total display time | 2BBD Stunden (120 Tage) |