CAPDIS-S2+ R4.5

CAPDIS-S2+ R4.5

Capacitive Voltage Detecting Systems with Relay Contacts

Item number: 2502134
The CAPDIS-S2+ R4.5 is an integrated Voltage Detecting Systems for checking for absence of... more
Product information "CAPDIS-S2+ R4.5"
The CAPDIS-S2+ R4.5 is an integrated Voltage Detecting Systems for checking for absence of voltage in medium-voltage switchgear in accordance with IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication and Signaling outputs.

Voltage Detecting Systems VDIS for medium voltage (1..52 kV)

Testing for absence of voltage in medium voltage switchgear according to IEC 61243-5 or IEC 62271-213 with integrated three-phase continuous display.

Maintenance-free due to self-monitoring

No periodic retesting required according to IEC 61243-55 and BGV A3, as the device permanently monitors the response threshold and displays it with three-stage voltage level indication (half, full, outlined flash arrow).

Complete lsolation monitoring of the capacitive divider

Complete, primary-side and secondary-side monitoring and display of the lsolation state of the capacitive voltage divider.

Adjustment facility for smart grid applications

Adjustment facility and monitoring of the capacitive divider for the standard-compliant response of the voltage test system and further processing of the voltage signals by smart grid systems (e.g. CAPDIS-M, IKI-50 ... ). Adjustable 6-stage capacitor switching module allows adjustment of the voltage divider and shows the correct setting in the display.

Integrated self-test function

No external test device is required to test for voltage freedom. Integrated function test by means of test button, according to patent DE 103 04 396. Clear display for primary voltage present and not present. Optional conductor break detection and ground monitoring.

Relay outputs and LED displays

For remote monitoring of the voltage states, two signal relays(changeover contacts) are integrated, which are operated with auxiliary voltage. The status of the relays is additionally indicated via LEDs in the front.

Integrated Y-interface

For further processing of the voltage signals via a smart grid system (e.g. IKlI50); connection via optional Y-cable.

Integrated three-phase measuring point

The device has a three-phase LRM measuring point. This serves as an interface for phase comparison and rotary field direction measurement (e.g. by means of universal tester type CAP-Phase, see data sheet CAP-Phase).

No battery required

Voltage test as well as self-test without battery or auxiliary voltage.
Device data
Article number2502134
Product designationCAPDIS-S2+ R4.5 Capacitive Voltage Detecting Systems with Relay Contacts
StandardIEC 61243-5, IEC 62271-213
Required data for orderRated operating voltage Un, coupling capacitance C1
Functions
Intrinsic safetyDevice is intrinsically safe
Maintenance testNo periodic inspections are necessary for this device
Broken lead detectionCan be activated/deactivated via DIP switches
Controls and display
Response time relay<= 1 s
Front displayMonochrome LC display and colored LEDs
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth48 x 96 x 37 mm
Cutout height x width45 x 92 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePanel mounting
Operating conditions
Operating temperature-25°C ... 55°C
Storage temperature-30°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz
Type of interfaceLRM
LifetimeMinimum 22 years (MTBF)
Signaling outputs
Connection of connecting cablesBy means of flat plug sleeve 4.8 x 0.8 mm or system plug (order separately)
Switching capacity relay250 VAC, 5 A (resistive load) / 30 VDC, 5 A / 250 VDC 0.3 A (resistive load)
Voltage supply
Auxiliary power supply24 - 230 V AC/DC +-10%
Power supply24 - 230 V AC/DC +- 10%; Power input < 1 Watt
Power consumption< 1 W
Insulation voltage1,5 kV
BatteryNo battery required