CAPDIS-4o_HF
Voltage transformer replacement for ohmic voltage sensors
with burden resistance 200 kOhm for sensors from Zelisko
Part-No.: 2502073_H002
Voltage transformer replacement for medium-voltage switchgears
Description
The CAPDIS-4o amplifier provides an output voltage of 3 x 100 VAC /sqrt (3) in combination with three ohmic coupling electrodes. The amplifier can therefore be used as a replacement for three inductive voltage transformers.
- economic alternative to voltage transformers in feeders
- minimum space requirement, no additional measuring field required
- no disassembly required for surge stress tests
- no ferroresonance risk
High device class accuracy
The device class accuracy is 0.5%. Higher accuracy on request.
Universal system components
- ohmic divider type OKE for air-insulated switchgears, series 12 kV, 24 kV or 36 kV
- ohmic divider type OAS for angle plug in gas-insulated switchgears, series 12 kV or 24 kV
- Voltage amplifier type CAPDIS-4o
OAS 12, OAS 24 with BNC
for asymmetric angle plugs
OAS 12, OAS 24 with BNC
for symmertric angle plugs
OKE 12, OKE 24 with BNC
for air-insulated systems
OKE 36 with BNC
for air-insulated systems
Technical data
Auxiliary voltage | 24 ... 240 VAC / DC |
Nominal frequency | 50 ... 60 Hz |
Power consumption | Approx. 7.5 VA |
Degree of protection | IP40 |
Input signal | 3.25 V/√3 |
Output signal | 3 x 100 VACeff, 3 x 0.5 VA |
Storage temperature | -25 ° C.. +85 ° C |
Operating temperature | -20 ° C.. +70 ° C |
Class accuracy | 1, according to IEC 60044 |
Weight | 600 g |
Dimensions | h x w x t = 115 x 175 x 49 mm |
Fixing | 35 mm standard rail |
Connection lines | Coaxial, standard length 3 m, 6 m |
Use Examples
- Connection of protective relays with conventional 100 VAC voltage measurement input
- Connection of universal measuring devices and network analyzers
- for critical safety applications (no ferroresonance)