CAPDIS-S2+ (R4.5)

CAPDIS-S2+ (R4.5)

Integrated capacitive voltage test system with relay contacts
Part-No.: 2502134
Voltage test system for medium voltage switchgear (VDS) with relay contacts  Basics... more
Product information "CAPDIS-S2+ (R4.5)"

Voltage test system for medium voltage switchgear (VDS) with relay contacts 

Basics

  • Voltage-free testing in medium voltage systems according to VDE 0682-T415 or IEC 61243-5
  • Integrated three-phase continuous display
  • Maintenance-free due to permanent self-monitoring
  • Intrinsically safe - no additional test equipment reuired
  • No battery or additional auxiliary voltage required for voltage test and self-test
  • Complete insulation monitoring of the capacitive divider
  • Simple adjustment of the capacitive voltage divider with capacitor circuit module
  • Simple self-test without battery or additional auxiliary voltage
  • Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.
  • Interface for smart grid systems for voltage measurement and fault monitoring
  • Active integrated conductor break detection

Specifics

Clear distinction from

  • Overvoltage
  • Operating voltage
  • Voltage below operating voltage
  • Voltage-free
  • Fault

Relay outputs and LED indicators

  • Two integrated signal relays (changers) for remote monitoring of voltage states
  • Additional status display of the relays via LEDs on the front side
  • Auxiliary voltage required for relay functions

Simple adjustment of the capacitive voltage divider

  • adjustable 6-stage capacitor circuit module

 

 

Technical Data

Applied Standard

VDE 0682 T 415 or IEC 61243-5 (integrated voltage test system)

Housing

Front panel installation

Dimensions

h x w x t = 48 x 96 x 37 mm

Recommended cutout

h x w = 45 x 92 mm

Operating Temperature

-25 ° C ... +75 ° C

Storage Temperature

-40 ° C ... +80 ° C

Protection

IP 54

LEDs

LED green corresponds to state relay 2; LED red corresponds to state relay 1

Auxiliary Voltage

24 - 230 VAC / DC +-10% Power Consumption: < 1 Watt

Relay Contacts

250 VAC, 5 A (ohmic load) / 30 VDC, 5 A / 250 VDC, 0.3 A (ohmic load), 1250 VA

Connection of the connection lines

By means of flat plug sleeve 4.8 x 0.8 mm or system plug (order separately)

 

Order Information

Basic Data

  • Nominal operating voltage UN
  • Coupling capacity C1

Universal switching modules C2m

  • Values low: (100, 470, 570, 1000, 3300, 4300 pF) Item No. 2501155
  • Values medium: (330, 2200, 2530,6800, 10000, 16800 pF) Item No. 2501156
  • Values high: (330, 2200, 2530, 10000, 22000, 32000 pF) Item No. 2501157
  • Further modules on request

 

 

 

Gas-insulated medium-voltage switchgear

Retrofitting in air-insulated medium voltage switchgear

Use of the CAPDIS-S2 also in air-insulated medium voltage switchgear

Integrated voltage test systems are almost always used in gas-insulated switchgears (new systems).

Increasingly, customers are also using the CAPDIS-S2 in air-insulated switchgear for retrofítting. This brings these customers significant advantages:

  • The voltage-free testing can be carried out when the system is closed.
  • This significantly improves both the personal and the plant safety .
  • The operator is thus protected from interference arcs .
Voltage-free testing with voltage testers
Voltage-free testing with voltage test systems