CAPDIS_top
Integrated capacitive voltage test system plug-in to the IKI-23
Item no.: 2502268
Voltage detection system (VDS) for retrofitting at medium voltage switchgears - pluggable to the IKI-23
Main functions
-
Test for voltage absence in medium voltage systems according to VDE 0682-T415 or IEC 61243-5
-
Maintenance-free due to permanent self-monitoring
-
Intrinsically safe - no additional test equipment required
Additional functionality
-
No battery or additional auxiliary voltage required
-
Complete insulation monitoring of the capacitive divider
-
Simple adjustment of the capacitive voltage divider with C2m capacitor module
-
Simple self-test without battery or additional auxiliary voltage
-
Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.
-
Interface for smart grid systems for voltage measurement and fault monitoring
Voltage level indication
Clear distinction from
-
Overvoltage
-
Nominal operating voltage
-
Voltage below operating voltage
-
Voltage absence
-
Fault
Simple adjustment of capacitive voltage divider
-
adjustable 6-stage c2m capacitor module
Technical Data
Designation | Integrated Voltage Detection System for retrofitting (VDS) |
Applied Standard | VDE 0682 T 415 or IEC 61243-5 |
Un | 1 - 52 kV |
Requirements | IKI-23 with LRM-Module |
Display | LCD |
Dry contacts output | No |
Maintenance test | Integrated |
Intrinsic safety | Yes |
Connections: | |
Dry contacts output | No |
Auxiliary power | Not needed |
Housing: | |
Mounting | Pluggable on IKI-23 with LRM-Module |
Dimensions | h x w x d = 50 x 55 x 16 mm |
Environmental conditions: | |
Operational temperature | -25 °C ... +75 °C |
Storage temperature | -40 °C ... +80 °C |
Degree of protection | IP 54 |