CAPDIS_top

CAPDIS_top

Integrated capacitive voltage test system plug-in to the IKI-23

Item no.: 2502268

Voltage detection system (VDS) for retrofitting at medium voltage switchgears - pluggable... more
Product information "CAPDIS_top"

Voltage detection system (VDS) for retrofitting at medium voltage switchgears - pluggable to the IKI-23



Main functions

  • Test for voltage absence in medium voltage systems according to VDE 0682-T415 or IEC 61243-5

  • Maintenance-free due to permanent self-monitoring

  • Intrinsically safe - no additional test equipment required

Additional functionality

  • No battery or additional auxiliary voltage required

  • Complete insulation monitoring of the capacitive divider

  • Simple adjustment of the capacitive voltage divider with C2m capacitor module

  • Simple self-test without battery or additional auxiliary voltage

  • Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.

  • Interface for smart grid systems for voltage measurement and fault monitoring

Voltage level indication

Clear distinction from

  • Overvoltage

  • Nominal operating voltage

  • Voltage below operating voltage

  • Voltage absence

  • Fault

Simple adjustment of capacitive voltage divider

  • adjustable 6-stage c2m capacitor module

 

Technical Data

Designation

Integrated Voltage Detection System for retrofitting (VDS)

Applied Standard

VDE 0682 T 415 or IEC 61243-5

Un

1 - 52 kV

Requirements

IKI-23 with LRM-Module

Display

LCD

Dry contacts output

No

Maintenance test

Integrated

Intrinsic safety

Yes

Connections:

 

Dry contacts output

No

Auxiliary power

Not needed

Housing:

 

Mounting

Pluggable on IKI-23 with LRM-Module

Dimensions

h x w x d = 50 x 55 x 16 mm

Environmental conditions:

 

Operational temperature

-25 °C ...  +75 °C

Storage temperature

-40 °C  ... +80 °C

Degree of protection

IP 54