CAPDIS-PI-LRM_R4
Retrofittable integrated capacitive voltage test system
for standard-compliant LRM interface
Item no.: 2501383
Retrofit Voltage detection system (VDS) for medium voltage switchgears - for LRM interfaces
Main functions
-
Test for voltage absence in medium voltage systems according to VDE 0682-T415 or IEC 61243-5
- Retrofitting of LRM interfaces with a passed maintenance test
-
Maintenance-free due to permanent self-monitoring
-
Intrinsically safe - no additional test equipment required
Additional functionality
-
No battery or additional auxiliary voltage required
-
Complete insulation monitoring of the capacitive divider
-
Simple adjustment of the capacitive voltage divider with C2m capacitor module
-
Simple self-test without battery or additional auxiliary voltage
-
Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.
-
Interface for smart grid systems for voltage measurement and fault monitoring
Voltage level indication
Clear distinction from
-
Overvoltage
-
Nominal operating voltage
-
Voltage below operating voltage
-
Voltage absence
-
Fault
Technical Data
Designation | Integrated Voltage Detection System (VDS) |
Applied Standard | VDE 0682 T 415 or IEC 61243-5 |
Un | 1 - 52 kV |
Voltage level | LRM |
Display | LCD |
Dry contacts output | No |
Maintenance test | Integrated |
Intrinsic safety | Yes |
Broken lead detection | Yes |
Auxiliary power | Not needed |
Housing: |
|
Mounting | Plug-in for LRM interfaces |
Dimensions | h x w x d = 52 x 111 x 38 mm |
Environmental conditions: |
|
Operational temperature | -25 °C ... +75 °C |
Storage temperature | -40 °C ... +80 °C |
Degree of protection | IP 54 |