CAPDIS-PI-HR_RR4_universal
Retrofittable integrated capacitive voltage test system
as retrofit solution for defective HR interfaces
Item no.: 2501384
Retrofit Voltage detection system (VDS) for medium voltage switchgears - for retrofitting old HR interfaces
Main functions
-
Test for voltage absence in medium voltage systems according to VDE 0682-T415 or IEC 61243-5
- Retrofit of old capacitive HR interfaces
-
Maintenance-free due to permanent self-monitoring
-
Intrinsically safe - no additional test equipment required
Additional functionality
-
No battery or additional auxiliary voltage required
-
Complete insulation monitoring of the capacitive divider
-
Simple adjustment of the capacitive voltage divider with C2m capacitor module
-
Simple self-test without battery or additional auxiliary voltage
-
Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.
-
Interface for smart grid systems for voltage measurement and fault monitoring
Voltage level indication
Clear distinction from
-
Overvoltage
-
Nominal operating voltage
-
Voltage below operating voltage
-
Voltage absence
-
Fault
Technical Data
Designation | Integrated Voltage Detection System (VDS) |
Applied Standard | VDE 0682 T 415 or IEC 61243-5 |
Un | 1 - 52 kV |
Voltage level | LRM |
Requirements | HR interface |
Display | LCD |
Maintenance test | Integrated |
Intrinsic safety | Yes |
Auxiliary power | Not needed |
Housing: | Mounting on HR interface |
Mounting | |
Dimensions | h x b x t = 52 x 111 x 38 mm |
Environmental conditions: |
|
Operational temperature | -25 °C ... +75 °C |
Storage temperature | -40 °C ... +80 °C |
Degree of protection | IP 54 |
Fast and cost-effective solution for defective HR interfaces
1. Initial situation
HR interface: repeat check required every 6 years; low life expectancy due to high insulation requirements.
2. Mounting CAPDIS-PI
3. Possibly adjust capacity
If the HR interface is defective, i.e. not all 3 full flash arrows appear with a standard CAPDIS-PI at the pending nominal voltage, an adjustable CAPDIS-PI RR4 is set up. The defective phases are reconfigured via DIP switches until three full flash arrows are displayed. No external measuring device is required for parameterization.
4. Result
- Repeat test-free voltage test system according to VDE 0682 T 415
- Testing for voltage-free without additional equipment
- Simplified earth fault detection at a glance
- Integrated self-test function
Bericht eines Anlagenbetreibers nach der Umrüstung auf CAPDIS-PI:
Defekte kapazitive HR-Schnittstellen, die bereits einen Isolationsverlust des kapazitiven Teilers angezeigt hatten, konnten durch Installation des speziellen Retrofit-Geräts Capdis-PI-RR3 in etwa zehn Minuten wieder komplett ertüchtigt werden, ohne dass die Anlage abgeschaltet oder zerlegt werden musste.
Durch die Komplettsanierung der hochohmigen, kapazitiven Schnittstellen mit den Capdis-PI-Spannungsprüfsystemen von Kries-Energietechnik haben die wir die Lebensdauer der kapazitiven Teiler erheblich verlängert, ohne die Lebensdauer der Schaltanlage zu vermindern.