CAPDIS-S1+_R4.5/HV
Voltage test system for high voltage applications
(52 ... 420 kV)
Item no.: 2502145_H001
Voltage detection system (VDS) for high voltage switchgears (52 - 420 kV)
Main functions
-
Test for voltage absence in high voltage systems according to VDE 0682-T415 or IEC 61243-5
-
Maintenance-free due to permanent self-monitoring
-
Intrinsically safe - no additional test equipment required
Additional functionality
-
No battery or additional auxiliary voltage required
-
Complete insulation monitoring of the capacitive divider
-
Active integrated conductor break detection
-
Simple adjustment of the capacitive voltage divider with C2m capacitor module
-
Simple self-test without battery or additional auxiliary voltage
-
Integrated three-phase measuring point for phase comparison, rotating field direction measurement, etc.
-
Interface for smart grid systems for voltage measurement and fault monitoring
Voltage levels indication
Clear distinction from
-
Overvoltage
-
Nominal operating voltage
-
Voltage below operating voltage
-
Voltage absence
-
Fault
Simple adjustment of capacitive voltage divider
-
adjustable 6-stage c2m capacitor module
Filter gegen EMV-Störungen
HV_EM_Absorber | Filter gegen EMV-Störungen, 10 cm, Installation direkt am C1, zusätzlich benötigt: Anschlusskabelsatz Artikelnummer: 2509398 |
Universal-Beschaltungsmodule C2m
C2m 6x (Standard) | Werte niedrig: (100, 470, 570, 1000, 3300, 4300 pF) Artikelnummer: 2501155 |
Werte mittel: (330, 2200, 2530, 6800, 10000, 16800 pF) Artikelnummer: 2501156 | |
Werte hoch: (330, 2200, 2530, 10000, 22000, 32000pF) Artikelnummer: 2501157 | |
weitere Module auf Anfrage |
Technical Data
Designation | Integrated Voltage Detection System (VDS) |
Applied Standard | VDE 0682 T 415 or IEC 61243-5 |
Un | 52 - 420 kV |
Voltage level | LRM |
Display | LCD |
Maintenance test | Integrated |
Intrinsic safety | Yes |
Broken lead detection | Yes |
Connections: | |
Dry contacts output | No |
Auxiliary power | Not needed |
Connection of the connection lines | By means flat plug sleeve 4.8 x 0.8 mm or system plug (order separately) |
Housing: | |
Mounting | Front panel mounting |
Dimensions | h x w x d = 48 x 96 x 37 mm |
Recommended panel cutout | h x w = 45 x 92 mm |
Environmental conditions: | |
Operational temperature | -25 °C ... +75 °C |
Storage temperature | -40 °C ... +80 °C |
Degree of protection | IP 54 |
Ordering Information
Basic
- Nominal operating voltage UN
- Coupling capacity C1
Universal switching modules C2m
- Values low: (100, 470, 570, 1000, 3300, 4300 pF) Item No. 2501155
- Values medium: (330, 2200, 2530,6800, 10000, 16800 pF) Item No. 2501156
- Values high: (330, 2200, 2530, 10000, 22000, 32000 pF) Item No. 2501157
- Further modules on request