Capacitive Voltage Sensors for Precise Voltage Measurement in Ring Main Units high accuracy... more
Product information "OAS24 R2"

Capacitive Voltage Sensors for Precise Voltage Measurement in Ring Main Units

  • high accuracy class voltage measurement combined with feeder controller IKI-50 or voltage amplifyer CAPDIS-4o
  • signal can be distributed to several evaluation units: up to five IKI-50 can be mounted to one set of OAS
  • secondary voltage 3.25 VAC
  • suitable for new systems and retrofit
  • sensors for SF6-plants: mounting in the T-plug instead of the end cap

 

Suitable for the following cable plugs:

Manufacturer Type
Südkabel SET 24
NKT CB 24-630 M12 for cable cross sections up to 300 mm²
NKT CB 36-1250 M16 for cable cross sections up to 630 mm² with 24 kV

Anschluss an IKI-50:

Nr. Artikelnummer Bezeichnung Länge Abschluss
2 2509392 Satz Koaxkabel, RG62 2 m 1) BNC-Winkel   2) Flachstecker
2 2509395 Satz Koaxkabel, RG62 6 m 1) BNC-Winkel   2) Flachstecker
2 2502339 Satz Koaxkabel, RG62 11 m 1) BNC-Winkel   2) Flachstecker

 

Nr. Artikelnummer Bezeichnung Länge Abschluss
3 2500486_H001 Verbindungskabel IKI-50 zu OAS/OKE 0,4 m 1) Flachstecker   2) Systemstecker

Anschluss an CAPDIS-4o:

Nr. Artikelnummer Bezeichnung Länge Abschluss
5 2509393_H003 Satz Koaxkabel, RG62 3 m 1) BNC-Winkel   2) Aderendhülse
5 2509393_H006 Satz Koaxkabel, RG62 6 m 1) BNC-Winkel   2) Aderendhülse
5 2509393_H015 Satz Koaxkabel, RG62 15 m 1) BNC-Winkel   2) Aderendhülse

Gerätedaten
Artikelnummer2045601_H001
Produktbezeichnung24 kV, 0,5 %, für NKT CB 24-630 M12, CB 36-1250 M16, Südkabel SET24
Einsatzbedingungen
Nennspannung24 kV
Sekundärspannung3,25 V
Teilerverhältnis200 M / 32,5 k
MontageNKT CB 24/630 M12
NKT ASTS 20-630 M12
Cellpack CTS 630