IKI-35_1A

IKI-35_1A

Self- or Dual-Powered Protection Relay for CTs ... / 1A

For automation and digitalization of distribution networks Protection-Relays are an intrinsic... more
Product information "IKI-35_1A"

For automation and digitalization of distribution networks Protection-Relays are an intrinsic solution. Digitalization level K4 (nodal automation) with minimum SAIDI only can be realized by self-acting intelligent protection relays which trip a faulty part of the network selectively.

  • Self-Powered relays are especially used in RMUs with circuit breakers where uninterruptable power supply is not necessarily available or does not have the same buffer time like in substations.
  • It also can be used in islanded networks with capability of black starting.
  • The selfpowered Protection Relay type IKI-35_1A is used for protection of distribution transformers and distribution feeders.

The ultra-compact design allows the installation in standard RMU-front panel without need of additional low voltage compartment. It can be installed directly to a low-power tripping coil with max. 24V/0,1Ws or through a mono-stable dry contact to any tripping coil.

 

By digital inputs and outputs and modbus-interface the device also can communicate with upstream and downstream protection in order to block or initiate tripping. The relay is used with conventional CTs ../1A.

For IKI-35_1 CTs are required with the following specification:

  • Ratio: 75/1A, 2.5VA
  • Class 5P10
  • BIL 0,72kV/3kV
  • Ith  25kA/1s acc. IEC 61869

 

General System-Data

Power-Frequency       

of network

selectable 50/60 Hz

Inherent time

<= 25 msec

must be added to lowest setting time

Product standard

IEC 60255-1:2009

 

Accuracy Current

 

±3% x (measured current) ± 0.005 x (nominal current)

Power up sensitivity

For self-powered mode, without auxiliary voltage, i.e. supply from CTs only:

  • single phase: 0.18A
  • two phase: 0.12A
  • three phase: 0.08A
for continuous current

 

Operation Temperature

 

-40 °C .. +70 °C

Storage Temperature

 

-40 °C .. +80 °C

Protection degree

IP40; front IP54

 

Mounting of Housing

Front-panel mounting

acc. DIN 43700

Dimensions

H*W*D

96*144*110 mm

Recommended Cut for Panel

H*W 92*138 mm

Weight

2.3 kg

 

Power-Supply (optional)

Universal

24..230VAC/DC; 0..60Hz; optional installed as dual-power-suppy in parallel to the CT-supply

CTs

In=1A

recommended: 5P20, min. 2.5VA

Digital-Outputs DO1, DO2

User configurable

function selectable: NC/NO, selectable logic: I> + Ie>; I>; Ie>; Trip

Digital-Inputs DI1, DI2

User configurable

External Fast-Trip; Block of Tripping

Temperature Inputs  

2*PT-100

2-/3-/4- wire connection to resistance temperature detector (RTD)

Communication

RS-485

Modbus RTU

Self-Powered Trip-Output

Active-output T1,T1   

Max. 24 V@ 0.1 Ws

Parallel Trip-Relay

Normally Open

250VAC@5A; 30VDC@5A; 220VDC@0,3A

Watch-Dog-Relay

User configurable

NO/NC/Off activated once microprocessor is defective

Device-type

IKI-35_1A

 

Software-type

Kries-Config

Configuration, event log and digital fault recorder download via PC

Dimensions

HMI

LCD + Backlight LED 

Dot-Matrix, max. 7 lines;

Status Indication and Parameterization of IKI-35_1A

LED1-5 , red /yellow

Status Indication 

 

USB-interface

Mini-USB

Parameterization via PC-Software Kries-Config

Event-Recorder

All Failure Events

20 events

Digital Fault Recorder

All Failure Events

10 events

 

Format

Comtrade 
 

Pre-trigger-time

selectable 0.1 .. 1 sec step 0.1 sec

 

Post-trigger-time

selectable 0.1 .. 1 sec step 0.1 sec

 

Sampling rate

1.6 kHz or 3.2 kHz for 50Hz
1.92kHz or 3.84kHz for 60Hz

Protection

Instantaneous Overcurrent Stage (50P) I>>, I>>>:        

 

 

pickup values

I>>>/In, I>>/In

selectable 0.1 .. 20 or deactivated

delay time

tI>>>, tI>>

selectable 0.05* ... 2 sec

Overcurrent Stage (51P) I>:

   

- DMT-pickup

I>/In

Ie>/In

selectable 0.1 .. 2 

selectable 0.05 ... 0.8

- Delay time

tI>

tIe>

selectable 0.3 .. 300 sec

selectable 0.05 .. 5 sec

- IDMT 1/2/3/4/5/6/7

trip characteristics for I> and Ie>:

selectable:    

1. IEC extremely inverse
2. IEC very inverse
3. IEC normal inverse
4. IEC long-time inverse
5. IEEE extremely inverse 
6. IEEE very inverse
7. IEEE normal inverse

 

reset characteristics:

selectable    

1. immediate
2. User-defined definite time
3. User-defined inverse time
4. IEEE extremely inverse
5. IEEE very inverse
6. IEEE normal inverse

Setting value

Starting value for IDMT

Time Multiplier Setting

I>/In

1.1 * Is

TMS

selectable 0.1 .. 2

Is = setting current

selectable 0.01 .. 1.5; step 0.01

Inrush (68)

Inrush-Algorithm                       

2nd Harmonic; Off

Thermal Overload T> (49) 

IB

selectable 1..600A; step 1A
 

Hmax

selectable  50.. 200%, step 1%

  K selectable  10.. 200%; step 1%

 

 

 