CAPDIS-PI-HR_RR4_universal

CAPDIS-PI-HR_RR4_universal

Retrofittable VDIS for defective HR interfaces

Item number: 2501384
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive... more
Product information "CAPDIS-PI-HR_RR4_universal"
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive interface into an integrated Voltage Detecting Systems according to IEC 61243-5 or IEC 62271-213.

Retrofitting without intervention in the switchgear 

Retrofitting to all interfaces according to IEC 61243-5 resp. IEC 62271-213 possible 

No battery required

 Voltage test as well as self-test without battery or auxiliary voltage

Maintenance-free 

No periodic maintenance test required due to permanent secondary-side insulation monitoring

Primary-side insulation monitoring of the capacitive divider 

Early detection and indication of insulation losses in the primary C1 of the capacitive divider 

Integrated self-test function 

No external test device is required to test for absence of voltage. Integrated auxiliary voltage independent function test, according to patent DE103 04 396. 

Integrated three-phase measuring point 

The device has a three-phase LR measuring point for phase comparison, rotating field direction measurement, etc.

Retrofit defective HR interfaces

that no longer meet maintenance test requirements.

Integrated Y-interface

For connection of an external directional fault detection system or load flow monitor (e.g. IKl-23, IKl-50), connection via optional Y-cable.
Device data
Article number2501384
Product designationCAPDIS-PI-HR_RR4 Retrofittable VDS for defective HR interfaces
StandardIEC 61243-5, IEC 62271-213
Required data for orderNominal voltage Un, size of coupling capacitor C1, type of interface present (HR, LRM, ...)
Controls and display
Front displayLC-Display
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth52 x 111 x 38 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePluggable
Operating conditions
Operating temperature-25°C ... 75°C
Storage temperature-25°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz, 16 2/3 Hz
Type of interfaceHR to LRM, HR-interface with failed maintenance test
LifetimeMinimum 33 years (MTBF)
Voltage supply
BatteryNo battery required