CAPDIS_top

CAPDIS_top

Capacitive Voltage Detecting Systems attachable to IKI-23

Item number: 2502268
The CAPDIS_top is an integrated Voltage Detecting Systems for checking for absence of voltage... more
Product information "CAPDIS_top"
The CAPDIS_top is an integrated Voltage Detecting Systems for checking for absence of voltage in medium-voltage switchgear in accordance with IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication. It can be plugged onto the IKI-23 fault indicator.

Retrofittable voltage testing system for IKl-23

CAPDIS_top is combined with the IKl-23 and thus converts the device into a fault indicator including voltage testing system. The CAPDIS-top is permanently placed on the capacitive measuring point.

Saving space

Both basic functions fault detection and voltage testing find space in a housing for standard cutout 45 x 92 mm.

Compliant with standards

CAPDIS_top is a complete voltage testing system according to DIN EN 61243-5 or VDE 61243-415


No battery required


Voltage testing as well as self-test without battery or auxiliary voltage.

Maintenance-free due to self-monitoring

No periodic retesting required according to VDE 0682-T 415 and BGV A3, as the device permanently monitors the response threshold and indicates it with a three-stage voltage level display (half, full and outlined flash arrow).

Complete insulation monitoring of the capacitive divider


Complete primary-side and secondary-side monitoring and display of the insulation status of the capacitive voltage divider.

Integrated self-test function


No external test device is required to test for voltage-free condition. Integrated function test by means of test button, in accordance with patent DE 103 04 396.


General data
Article number2502268
Product designationCAPDIS_top, capacitive Voltage Detecting Systems attachable to IKI-23
StandardIEC 61243-5, IEC 62271-213
Functions
Intrinsic safetyDevice is intrinsically safe
Maintenance testNo periodic inspections are necessary for this device.
Display and HMI interfaces
Voltage test
Front displayLC-Display
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth50 x 55 x 16 mm
Cutout height x width45 x 92 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePluggable
Environmental conditions
Operating temperature-25°C ... 55°C
Storage temperature-30°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz
Type of interfaceLRM
LifetimeMinimum 31 years (MTBF)
Voltage supply
Power supplyNo auxiliary power supply needed
BatteryNo battery required