CAPDIS-S1_55 (R5)

CAPDIS-S1_55 (R5)

Capacitive Voltage Detecting Systems with Partial Discharge Detection

Item number: 2502145_H004
The CAPDIS-S1_55 (R5) is an integrated Voltage Detecting Systems for checking for absence of... more
Product information "CAPDIS-S1_55 (R5)"
The CAPDIS-S1_55 (R5) is an integrated Voltage Detecting Systems for checking for absence of voltage in medium-voltage switchgear according to IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication. It also allows the detection of partial discharges in the transformer station and its surroundings.

Voltage Detecting Systems VDIS for medium voltage (1..52 kV)


Testing for absence of voltage in medium voltage switchgear according to IEC 61243-5 or IEC 62271-213 with integrated three-phase continuous display.


Maintenance-free due to self-monitoring


No periodic retesting required according to  IEC 62271-213 and BGV A3, as the device permanently monitors the response threshold and indicates it with a three-stage voltage level display (half, full and outlined flash arrow).

Voltage testing for power systems

Voltage testing system according to protection device standard IEC 60255 and voltage tester standard IEC 61243-5 or IEC 62271-213. The CAPDIS-S1_55 is specially dimensioned for use in power systems and absorbs high-frequency disturbance variables from atmospheric surge voltage loads, backfiring and resonance oscillations at all inputs and outputs. This also prevents the propagation of interference to the rest of the secondary equipment. The extended immunity to interference also allows the CAPDIS-S1_55 to be used for safety-relevant functions.

Partial discharge detection


Critical partial discharge levels are detected and shown in the display as a warning message. The sensitivity of the PD detection is set via a DIP switch on the back of the device or also deactivated. A socket behind the front flap is available for PD diagnostics.

Complete insulation monitoring of the capacitive divider


Complete primary-side and secondary-side monitoring and display of the insulation status of the capacitive voltage divider.

Adjustment capability for smart grid applications


Adjustment capability and monitoring of the capacitive divider for standard voltage test system response and further processing of voltage signals by smart grid systems (e.g. CAPDIS-M, IKI-50, IKI-22...). Adjustable 6-stage capacitor switching module allows adjustment of the voltage divider and shows the correct setting on the display.

Integrated self-test function


No external test equipment is required to test for voltage freedom. Integrated function test by means of test button, according to patent DE 103 04 396. Clear display for primary voltage present and not present. Optional conductor break detection and ground monitoring.

Integrated Y-interface


For further processing of voltage signals via a smart grid system (e.g. IKI-50); connection via optional Y-cable. Integrated three-phase measuring point The device has a three-phase LRM measuring point. This serves as an interface for phase comparison and rotary field direction measurement (e.g. by means of universal tester type CAP-Phase, see data sheet CAP-Phase).

No battery required


Voltage test as well as self-test without battery or auxiliary voltage.
General data
Article number2502145_H004
Product designationCAPDIS-S1_55 (R5) Capacitive Voltage Detecting Systems with Partial Discharge Detection
StandardIEC 61243-5, IEC 62271-213, IEC 60255-1
Required data for orderNominal voltage Un, coupling capacitance C1
Functions
Intrinsic safetyDevice is intrinsically safe
Maintenance testNo periodic inspections are necessary for this device.
Broken lead detectionCan be activated/deactivated via DIP switches
Partial discharge detection
  • Device detects partial discharges
  • 4 sensitivity levels adjustable
.
Display and HMI interfaces
Front displayLC-Display
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth48 x 96 x 37 mm
Cutout height x width45 x 92 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePanel mounting
Environmental conditions
Operating temperature-25°C ... 55°C
Storage temperature-30°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz
Type of interfaceLRM
LifetimeMinimum 31 years (MTBF)
Voltage supply
Power supplyNo auxiliary power supply needed
BatteryNo battery required