This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Track device being used

CAPDIS-S2+ R4.5
Capacitive Voltage Detecting Systems with Relay Contacts
Item number: 2502134
Item number: 2502134
The CAPDIS-S2+ R4.5 is an integrated Voltage Detecting Systems for checking for absence of... more
Product information "CAPDIS-S2+ R4.5"
The CAPDIS-S2+ R4.5 is an integrated Voltage Detecting Systems for checking for absence of voltage in medium-voltage switchgear in accordance with IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication and Signaling outputs.
Voltage Detecting Systems VDIS for medium voltage (1..52 kV)
Testing for absence of voltage in medium voltage switchgear according to IEC 61243-5 or IEC 62271-213 with integrated three-phase continuous display.Maintenance-free due to self-monitoring
No periodic retesting required according to IEC 61243-55 and BGV A3, as the device permanently monitors the response threshold and displays it with three-stage voltage level indication (half, full, outlined flash arrow).Complete lsolation monitoring of the capacitive divider
Complete, primary-side and secondary-side monitoring and display of the lsolation state of the capacitive voltage divider.Adjustment facility for smart grid applications
Adjustment facility and monitoring of the capacitive divider for the standard-compliant response of the voltage test system and further processing of the voltage signals by smart grid systems (e.g. CAPDIS-M, IKI-50 ... ). Adjustable 6-stage capacitor switching module allows adjustment of the voltage divider and shows the correct setting in the display.Integrated self-test function
No external test device is required to test for voltage freedom. Integrated function test by means of test button, according to patent DE 103 04 396. Clear display for primary voltage present and not present. Optional conductor break detection and ground monitoring.Relay outputs and LED displays
For remote monitoring of the voltage states, two signal relays(changeover contacts) are integrated, which are operated with auxiliary voltage. The status of the relays is additionally indicated via LEDs in the front.Integrated Y-interface
For further processing of the voltage signals via a smart grid system (e.g. IKlI50); connection via optional Y-cable.Integrated three-phase measuring point
The device has a three-phase LRM measuring point. This serves as an interface for phase comparison and rotary field direction measurement (e.g. by means of universal tester type CAP-Phase, see data sheet CAP-Phase).No battery required
Voltage test as well as self-test without battery or auxiliary voltage.Device data | |
Article number | 2502134 |
Product designation | CAPDIS-S2+ R4.5 Capacitive Voltage Detecting Systems with Relay Contacts |
Standard | IEC 61243-5, IEC 62271-213 |
Required data for order | Rated operating voltage Un, coupling capacitance C1 |
Functions | |
Intrinsic safety | Device is intrinsically safe |
Maintenance test | No periodic inspections are necessary for this device |
Broken lead detection | Can be activated/deactivated via DIP switches |
Controls and display | |
Response time relay | <= 1 s |
Front display | Monochrome LC display and colored LEDs |
Controls | Self-test button |
Dimensions and type of installation | |
Case height x width x depth | 48 x 96 x 37 mm |
Cutout height x width | 45 x 92 mm |
Norm cutout dimensions | DIN IEC 61554:2002-08 |
Installation type | Panel mounting |
Operating conditions | |
Operating temperature | -25°C ... 55°C |
Storage temperature | -30°C ... 75°C |
Protection class | IP54 |
Voltage level | 1..52 kV (Medium-voltage) |
Rated frequency | 50 Hz, 60 Hz |
Type of interface | LRM |
Lifetime | Minimum 22 years (MTBF) |
Signaling outputs | |
Connection of connecting cables | By means of flat plug sleeve 4.8 x 0.8 mm or system plug (order separately) |
Switching capacity relay | 250 VAC, 5 A (resistive load) / 30 VDC, 5 A / 250 VDC 0.3 A (resistive load) |
Voltage supply | |
Auxiliary power supply | 24 - 230 V AC/DC +-10% |
Power supply | 24 - 230 V AC/DC +- 10%; Power input < 1 Watt |
Power consumption | < 1 W |
Insulation voltage | 1,5 kV |
Battery | No battery required |