CAPDIS-S2_55 (R5)

CAPDIS-S2_55 (R5)

Capacitive Voltage Detecting Systems with Relay Contacts for Protection Applications, with Partial Discharge Detection

Item number: 2502134_H008
The CAPDIS-S2_55 (R5) is an integrated Voltage Detecting Systems for checking for absence of... more
Product information "CAPDIS-S2_55 (R5)"
The CAPDIS-S2_55 (R5) is an integrated Voltage Detecting Systems for checking for absence of voltage in medium voltage switchgear applications according to IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication and Signaling outputs. It also allows detection of partial discharges in the station and its surroundings.

Voltage Detecting Systems VDIS for Medium Voltage (1..52 kV)

Testing for absence of voltage in medium voltage switchgear according to IEC 61243-5 or IEC 62271-213 with integrated three-phase continuous indication.

Application in power switchgear and for protection purposes

As an active element of the protection chain

Fail-safe voltage testing and protection function

Voltage Detecting Systems according to protection device standard IEC 60255 and voltage tester standard IEC 61243-5 resp. IEC 62271-213. The CAPDIS-S2_55 is specially dimensioned for use in power systems as well as for protection purposes and absorbs high-frequency disturbance variables from atmospheric surge voltage loads, backfiring and resonance oscillations at all inputs and outputs. This also prevents the propagation of interference to the rest of the secondary equipment. The extended immunity to interference also allows the CAPDIS-S2_55 to be used for safety-relevant functions.

Switching fault protection

The propagation of decentralized feeders requires the installation of reverse voltage detection with switching fault protection in substations and protection stations. Reverse voltage detection provides personnel safety and switching fault protection by interlocking the grounding switch when reverse voltage is present.

Partial discharge detection

Critical partial discharge levels are detected, indicated on the display and output via the relay collective fault signal. The sensitivity of the PD detection is set or also deactivated via a DIP switch on the rear of the device. A socket behind the front flap is available for PD diagnostics.

Islanding network warning

In substations, for the islanding network warning, it must also be checked with the circuit breaker open whether reverse voltage is present. If this is the case, an islanding warning is generated in the field control and protection device, which prevents automatic connection during an AWE (automatic reclosure) when reverse voltage is present.

Protective device standard IEC 60255

Fulfills the IEC 60255 standard and is thus authorized for protection and safety functions. Integrated interface to the CAPDIS-M voltage monitoring module.

Maintenance-free, complete self-monitoring

The 3-level voltage display exempts the CAPDIS-S2_55 from repetition testing in accordance with IEC 61243-5 or IEC 62271-213 and BGV A3. The device also does not require a battery for the self-test according patent DE 103 04 396.

Protection relay outputs and LED indicators

Two power relays (changeover contacts) are operated with universal auxiliary voltage. Status indication by means of LEDs in the front.
Device data
Article number2502134_H008
Product designationCAPDIS-S2_55 (R5) Capacitive Voltage Detecting Systems with Relay Contacts for Protection Applications | with Partial Discharge Detection
StandardIEC 61243-5, IEC 62271-213, IEC 60255-1
Required data for orderRated operating voltage Un, coupling capacitance C1
Functions
Intrinsic safetyDevice is intrinsically safe
Maintenance testNo periodic inspections are necessary for this device
Broken lead detectionCan be activated/deactivated via DIP switches
Partial discharge detection
  • Device detects partial discharges
  • 4 sensitivity levels adjustable
  • Remote indication of partial discharge e.g. to IKI-23, IKI-50_1F R2, IKI-50_1F R2e or IKI-55 for partial discharge trend detection
Controls and display
Response time relay<= 0,2 s
Front displayMonochrome LC display and colored LEDs
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth48 x 96 x 37 mm
Cutout height x width45 x 92 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePanel mounting
Operating conditions
Operating temperature-25°C ... 55°C
Storage temperature-30°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz
Type of interfaceLRM
LifetimeMinimum 22 years (MTBF)
Signaling outputs
Connection of connecting cablesBy means of flat plug sleeve 4.8 x 0.8 mm or system plug (order separately)
Switching capacity relay250 VAC, 5 A (resistive load) / 30 VDC, 5 A / 250 VDC 0.3 A (resistive load)
Voltage supply
Auxiliary power supply24 - 230 V AC/DC +-10%
Power supply24 - 230 V AC/DC +- 10%; Power input < 1 Watt
Power consumption< 1 W
Insulation voltage2 kV
BatteryNo battery required