IKI-Overhead R2

IKI-Overhead R2

Fault indicator for overhead line

Item number: See variants
With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus integrated... more
Product information "IKI-Overhead R2"
With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus integrated into the overall protection concept to minimize downtime. Fault indication is provided locally via strong LEDs and optionally via remote transmission to a central control station.

Fault detection of all typical overhead line faults

Short circuits, transients and ground faults

Ultra-bright LED display

Visibility cone 360°, visible even in bright sunlight

Easy installation using actuating rod

Integrated torque indicator shows correct installation. No additional tools required.

Reliable fault detection

Overcurrent and short-circuit via to independent current/time characteristic; short and earth (short) circuit detection; high impedance fault detection by dI/dT detection; inrush suppression; fault confirmation by monitoring for disconnection via integrated voltage sensor

Simple parameter setting by DIP switch

Response current (automatic or fixed thresholds 200 - 600 A). Reset time (2 - 8 h, manual or automatic after load current recovery). Access to DIP switches possible without tools.

Long life

due to high quality lithium battery, nanowatt technology and corrosion-free housing.

Easy installation

Torque indicator for safe mounting
.

IKI-Overhead R2 with remote signalling: Radio and Butler versions

All communication elements are directly installed in the overhead line indicators. Therefore, no additional telecontrol unit mounted on the pole is required.

Easy connection to the control center via IEC 60870-5-104

With the optionally available SMS gateway, all installed IKI overhead R2 are connected to the control center or the PONLINE system and integrated

Detection of conductor breakage in the overhead line

Detection of conductor breakage without fault current

Transmission of load current values

Instantaneous or average values are transmitted cyclically

Remote parameterization of settings possible

Communication principle

Up to 8 IKI overhead radios communicate with one IKI overhead butler via short-range radio. The IKI overhead butler communicates via GSM with the PONLINE master server or any SMS receivers. The PONLINE master server can be connected to the control room via an IEC 60870-5-104 interface.

Principle of fault detection with remote signalling

Faults are detected and reported right up to the fault location in each case

Display of all relevant status information

In conjunction with PONLINE®, all important information (faults and load flow) from the overhead line network, such as all types of faults and load flow information, is recorded and transmitted.
Device data
Article numberIKI-Overhead_R2
Product designationIKI-Overhead R2 Fault indicator for overhead line
Display
Display VisibilityApprox. 50-100 m in bright sunlight
approx. 500 m at night
Display flashing frequency30 per minute
Brightness display13 Candela
Dimensions and installation instructions
Case height x width x depth250 x 104 x 145 mm
Conductor cross section20 - 490 mm²; 5 - 35 mm diameter
Operating conditions
Operating temperature-30°C ... 75°C
Storage temperature-30°C ... 80°C
Protection classIP67
Voltage levelApplicable up to 36 kV
Maximum height operation4500 m above sea level
Maximum wind force70 m/s
Fault detection
Short circuit detection I>>
Threshold current short-circuit detection I>> [A]200, 400, 600
Automatic response threshold Short circuit detection
Threshold time short-circuit detection I>> [ms]80, 150
Threshold time short-circuit detection (I>>) adjustable via DIP [ms]80, 150
Waiting time after current switch-off (short-circuit detection) [ms]200
Earth short-circuit detection Ie>>
Reset setting2, 4, 8 h
ResetTime, manually by actuating rod, automatically after load current return > 3 A
Communication
Frequency bands4
GSM network2G
SIM card formatStandard-SIM (Mini-SIM)
Power supply
BatteryLithium battery
Battery lifeApprox. 15 years
Battery total display time2BBD Stunden (120 Tage)