CAPDIS-PI-HR_RR4_universal

CAPDIS-PI-HR_RR4_universal

Retrofittable VDIS for defective HR interfaces, 90° rotateable

Item number: 2501384_H001
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive... more
Product information "CAPDIS-PI-HR_RR4_universal"
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive interface into an integrated Voltage Detecting Systems according to IEC 61243-5 or IEC 62271-213.

Retrofitting without intervention in the switchgear 

Retrofitting to all interfaces according to IEC 61243-5 resp. IEC 62271-213 possible 

No battery required

 Voltage test as well as self-test without battery or auxiliary voltage

Maintenance-free 

No periodic maintenance test required due to permanent secondary-side insulation monitoring

Primary-side insulation monitoring of the capacitive divider 

Early detection and indication of insulation losses in the primary C1 of the capacitive divider 

Integrated self-test function 

No external test device is required to test for absence of voltage. Integrated auxiliary voltage independent function test, according to patent DE 103 04 396. 

Integrated three-phase measuring point 

The device has a three-phase LR measuring point for phase comparison, rotating field direction measurement, etc.

Retrofit defective HR interfaces

that no longer meet maintenance test requirements.

Integrated Y-interface

For connection of an external directional fault detection system or load flow monitor (e.g. IKl-23, IKl-50), connection via optional Y-cable.

Device rotatable about 90 degrees

For vertical installations
Device data
Article number2501384_H001
Product designationCAPDIS-PI-HR_RR4 Retrofittable VDS for defective HR interfaces
StandardIEC 61243-5, IEC 62271-213
Required data for orderNominal voltage Un, size of coupling capacitor C1, type of interface present (HR, LRM, ...)
Functions
Intrinsic safetyDevice is intrinsically safe
Maintenance testNo periodic inspections are required for this device
System connector (ankled)
Rotatable90°
Controls and display
Front displayLC-Display
ControlsSelf-test button
Dimensions and type of installation
Case height x width x depth52 x 111 x 38 mm
Norm cutout dimensionsDIN IEC 61554:2002-08
Installation typePluggable
Operating conditions
Operating temperature-25°C ... 75°C
Storage temperature-25°C ... 75°C
Protection classIP54
Voltage level1..52 kV (Medium-voltage)
Rated frequency50 Hz, 60 Hz, 16 2/3 Hz
Type of interfaceHR to LRM, HR-interface with failed maintenance test
LifetimeMinimum 33 years (MTBF)
Voltage supply
BatteryNo battery required