Cookie preferences
This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Track device being used
CAPDIS-PI-HR_RR4_universal
Retrofittable VDIS for defective HR interfaces, connecting lines L1/L3 - length 300 mm
Item number: 2501384_H002
Item number: 2501384_H002
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive... more
Product information "CAPDIS-PI-HR_RR4_universal"
Retrofittable Voltage Detecting Systems for medium voltage (VDIS). Conversion of an capacitive interface into an integrated Voltage Detecting Systems according to IEC 61243-5 or IEC 62271-213.
Retrofitting without intervention in the switchgear
Retrofitting to all interfaces according to IEC 61243-5 resp. IEC 62271-213 possibleNo battery required
Voltage test as well as self-test without battery or auxiliary voltageMaintenance-free
No periodic maintenance test required due to permanent secondary-side insulation monitoringPrimary-side insulation monitoring of the capacitive divider
Early detection and indication of insulation losses in the primary C1 of the capacitive dividerIntegrated self-test function
No external test device is required to test for absence of voltage. Integrated auxiliary voltage independent function test, according to patent DE 103 04 396.Integrated three-phase measuring point
The device has a three-phase LR measuring point for phase comparison, rotating field direction measurement, etc.Retrofit defective HR interfaces
that no longer meet maintenance test requirements.Integrated Y-interface
For connection of an external directional fault detection system or load flow monitor (e.g. IKl-23, IKl-50), connection via optional Y-cable.Extra-long connection cables
The connections for L1 and L3 are designed with a length of 300 mm in order to be able to connect interfaces that are far apart.Device data | |
Article number | 2501384_H002 |
Product designation | CAPDIS-PI-HR_RR4 Retrofittable VDS for defective HR interfaces |
Standard | IEC 61243-5, IEC 62271-213 |
Required data for order | Nominal voltage Un, size of coupling capacitor C1, type of interface present (HR, LRM, ...) |
Functions | |
Intrinsic safety | Device is intrinsically safe |
Maintenance test | No periodic inspections are required for this device |
System connector (ankled) | ✓ |
Rotatable | 180° |
Controls and display | |
Front display | LC-Display |
Controls | Self-test button |
Dimensions and type of installation | |
Case height x width x depth | 52 x 111 x 38 mm |
Norm cutout dimensions | DIN IEC 61554:2002-08 |
Installation type | Pluggable |
Operating conditions | |
Operating temperature | -25°C ... 75°C |
Storage temperature | -25°C ... 75°C |
Protection class | IP54 |
Voltage level | 1..52 kV (Medium-voltage) |
Rated frequency | 50 Hz, 60 Hz, 16 2/3 Hz |
Type of interface | HR to LRM, HR-interface with failed maintenance test |
Lifetime | Minimum 33 years (MTBF) |
Voltage supply | |
Battery | No battery required |