VOIS R+

VOIS R+

C2m = 10 000 pF, control line pluggable, no ground wire

Item number: 2502063_H014

The VOIS-R is an integrated Voltage Detecting Systems VDIS for checking for absence of voltage... more
Product information "VOIS R+"

The VOIS-R is an integrated Voltage Detecting Systems VDIS for checking for absence of voltage in medium voltage switchgear according to IEC 62271-213:2021 (or IEC 61243-5) with integrated three-phase continuous indication as well as a signalling contact.

Voltage indication system for medium voltage (VDIS)

Integrated three-phase voltage indication system for medium voltage switchgear acc. IEC 61243-5 and IEC 62271-213

Relay output

changeover contact for status indication

No battery required

Voltage indication without battery or auxiliary voltage

Integrated three-phase measuring point

The device has a three-phase LR measuring point for phase comparison, rotating field direction measurement, etc.

Convenient alternative

to plug-in voltage indicators.

 

Information about vulnerabilities of this product can be reported and received on this website: te.com/productsecurity.

Device data
Article number 2502063_H014
Quantity unit Piece
Product designation Integrated Voltage Detecting Systems VOIS R+ with relay contact
C2m = 10 000 pF, control line pluggable, no ground wire
Required data for order Primary capacitance C1 of the coupling electrode Rated voltage UN
Configuration
Switching capacity C2m 10,000 pF
System connector (ankled)
Control line (Relay output, auxiliary voltage) included Included
Earthing wire included -
Functionalities
Voltage test
Response time relay Max. 1 s
Dimensions
Case height x width x depth 48 x 96 x 37 mm
Cutout height x width 45 x 45 mm
Norm cutout dimensions DIN 43700
Installation type Panel mounting
Operating conditions
Operating temperature -25°C ... 55°C
Storage temperature -30°C ... 80°C
Protection class IP54
Voltage level 1..52 kV (Medium-voltage)
Rated frequency 50 Hz, 60 Hz
Type of interface LRM
Signaling outputs
Connection of connecting cables 4.8 x 0.8 mm flat receptacles or system connectors
Signal outputs 1
Technical data signal output 1 1 changeover contact, voltage present / absence of voltage
Voltage supply
Auxiliary power supply 24 .. 230 VAC/DC
Power consumption 1 W
Battery No battery required