OKE36

OKE36

Resistive voltage sensor, 36 kV, 0.5 %, for retrofit, BNC connection

Item number: 2045228
Ohmic terminations provide a compact means of precise voltage measurement in transformer... more
Product information "OKE36"
Ohmic terminations provide a compact means of precise voltage measurement in transformer stations. They are typically installed in air-insulated switchgears and can be used in combination with e.g. CAPDIS-4o as a voltage transformer substitute or with the IKI-50 for voltage measurement.

  • Sensors for air-insulated switchgears 12 - 36 kV
  • Mounting as a coupling electrode within the switchgear or cable room.
  • Voltage measurement in conjunction with the control device for the transformer station Grid-Inspector IKI-50 or the voltage amplifier CAPDIS-4o.
  • Distribution of the signal to multiple evaluation devices possible: connection of up to five IKI-50 on a set of OKE
  • Secondary voltage 3.25 VAC
  • Suitable for new installations and retrofits
  • Pluggable BNC connector for secondary side
  • OKE12 and OKE24 can be attached directly to air-insulated end closures via optional coupling electrode mounting set, without having to intervene in the switchgear.

Version

Operating voltage 36 kV, measured value deviation 0.5 %.
Device data
Article number2045228
Product designationOKE 36, 36 kV | 0.5 %
Dimensions
MountingFor retrofit air-insulated switchgears
Rated voltage36 kV
Secondary voltage3.25 V
Divider ratio300 M / 32,5 k
MountingFor retrofit air-insulated switchgears