Split-core CT, directional, for measured value acquisition, for unshielded ground cable terminations, set

Item number: 2500461
Split-core CT, directional, for measured value acquisition, for unshielded cable terminations.... more
Product information "IKI-LUM-ISO"
Split-core CT, directional, for measured value acquisition, for unshielded cable terminations. IKI current transformers are specially designed for use with IKI fault indicators, IKI grid-controllers and IKI transformer protection devices. IKI current transformers are designed for maximum current ranges. They are easy to mount and can be quickly connected to the IKI devices via suitable connection cables.


- Marking of the load flow direction
- Easy opening and closing due to push lock
- Fixation on the cable with cable tie
- For insulated oder shielded underground MV-cables up to Un = 15kV
General data
Article number2500461
Quantity unitPiece
Product designationSplit-core CT for IKI-LUM-ISO (set) | directional | for measured value acquisition | for unshielded ground cable terminations | Ø 52mm
Usable withIKI-22, IKI-23, IKI-35, IKI-50, IKI-55
Operating conditions
Protection classIP54
Inner diameter52 mm
Transmission ratio2000 / 0.1
Load power0,2 VA @ 600 A
Thermal maximum current27 kA
Maximum continuous thermal current650 A
Directional current sensing
Installation locationNon-screened oil cable terminations