This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Track device being used
IKI-LUM_30_d92
Split-core CT, non-directional, for IKI-30, set
Item number: 2512288_H001
Item number: 2512288_H001
IKI current transformers are specially designed for use with IKI fault indicators, IKI... more
Product information "IKI-LUM_30_d92"
IKI current transformers are specially designed for use with IKI fault indicators, IKI grid-controllers and IKI transformer protection devices. IKI current transformers are designed for maximum current ranges. They are easy to mount and can be quickly connected to the IKI devices via suitable connection cables.
Variant to mount directly on screened cables.
Variant to mount directly on screened cables.
General data | |
Article number | 2512288_H001 |
Quantity unit | Set with 3 pieces |
Product designation | split-core CT IKI-LUM_30_d92 (set) | non-directional | for IKI-30 | Ø 92mm |
Usable with | IKI-30E_1_S092, IKI-30E_1_S092_DIW |
Operating conditions | |
Protection class | IP54 |
Insulation voltage | 3 kV |
Applicable at nominal frequency | 50 Hz, 60 Hz |
Inner diameter | 92 mm |
Transmission ratio | 10 A / 0.002 A |
Load power | 0.02 VA @ 10 A |
Thermal maximum current | 23 kA |
Maximum continuous thermal current | 600 A |
Directional current sensing | - |
Installation location | Screened cables |