IKI-LUM d92, 1%

CT for bushings, 1% deviation, directional, for measured value acquisition, for Siemens switchgears, set

Item number: 2512106_H004_S001
IKI current transformers are specially designed for use with IKI fault indicators, IKI... more
Product information "IKI-LUM d92, 1%"
IKI current transformers are specially designed for use with IKI fault indicators, IKI grid-controllers and IKI transformer protection devices. IKI current transformers are designed for maximum current ranges. They are easy to mount and can be quickly connected to the IKI devices via suitable connection cables.

  • Steckbares Anschlusskabel für einfache Installation
  • Kennzeichnung der Lastflussrichtung
  • Einfaches Öffnen und Schließen durch Druckverschluss
  • Befestigung am Kabel mit Kabelbinder
  • Kann auf C-Kegel-Durchführungen zusammen mit Durchführungshülsen verwendet werden
This current transformer has a higher accuracy. In conjunction with the IKI-50_1F R2, precise measured value acquisition is possible.
General data
Article number2512106_H004_S001
Quantity unitSet with 3 pieces
Product designationIKI-LUM_d92 1% CT for bushings (set) for SIEMENS switchgears
General data
Usable withIKI-50_1F R2
Operating conditions
Protection classIP54
Operating conditions
Class accuracyClass 1 (in conjunction with IKI-50_1F R2)
Applicable at nominal frequency50 Hz, 60 Hz
Inner diameter92 mm
Transmission ratio2000 / 1
Load power0.2 VA @ 600 A
Thermal maximum current27 kA
Note on thermal maximum currentValue applies with connected IKI-50_1F R2
Maximum continuous thermal current650 A
Insulation voltage transformer3 kV
Directional current sensing
Installation locationScreened cables, Bushing of SF6-Switchgear