IKI-LUM d92

IKI-LUM d92

CT for bushings, directional, for measured value acquisition, for C-cone, set

Item number: 2512106_H003
IKI current transformers are specially designed for use with IKI fault indicators, IKI... more
Product information "IKI-LUM d92"
IKI current transformers are specially designed for use with IKI fault indicators, IKI grid-controllers and IKI transformer protection devices. IKI current transformers are designed for maximum current ranges. They are easy to mount and can be quickly connected to the IKI devices via suitable connection cables.

  • steckbare Anschlussleitung für leichte Montage
  • Kennzeichnung der Lastflussrichtung
  • leichtes Öffnen und Schließen durch Druckverschluss
  • Fixierung am Kabel mit Kabelbinder
  • einsetzbar auf C-Konus-Durchführungen zusammen mit Durchführungs-Hülsen
General data
Article number2512106_H003
Quantity unitSet with 3 pieces
Product designationIKI-LUM_d92 Split-Core Transducer for C-Cone-Bushings (set) | Ø 92mm
General data
Usable withIKI-22, IKI-23, IKI-35, IKI-50, IKI-50_1F R2, IKI-50_1F R2e, IKI-55
Operating conditions
Protection classIP54
Operating conditions
Applicable at nominal frequency50 Hz, 60 Hz
Inner diameter92 mm
Transmission ratio2000 / 1
Load power0.2 VA @ 600 A
Thermal maximum current27 kA
Maximum continuous thermal current650 A
Insulation voltage transformer3 kV
Directional current sensing
Installation locationBushing of SF6-Switchgear