This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Track device being used
IKI-20B1
Short-circuit / earth short-circuit indicator, battery buffered, 1 relay output changeover contact
Item number: 2500971
Variants Item number: 2500971
The IKI-20 is suitable for the detection, indication and remote signalling of short circuits in... more
Product information "IKI-20B1"
The IKI-20 is suitable for the detection, indication and remote signalling of short circuits in power distribution networks. In addition, in power distribution networks with rigidly, low-resistance or short-time low-resistance grounded neutral point, the detection, indication and remote signalling of ground short-circuits is possible. Non-directional earth faults can be indicated in cleared or isolated networks.
The IKI-20 is maintenance-free because the power supply is provided by the current transformers.Buffering of power supply
The IKI-20 is maintenance-free because the power supply is provided by the current transformers.
Measurement functions and display
- Reliable measured value processing through independent overcurrent-time characteristic (UMZ measurement function)
- True current measurement
- Self-explanatory LCD-. symbols
- additional very bright LED flashing display
Universal setting option of operating parameters
- response current and response time separately for short circuit and earth short circuit
- reset mode resp. reset time
- Relay functions duration or wiping contact
Self test
- Function test on site by means of test button or remotely controllable via auxiliary input
Operation in ring and beam network (without switching)
- Differentiated display of first and second fault event in networks with AWE
Buffering of power supply
- Using integrated lithium battery (lifetime >17 years with current transformers not connected)
Relay outputs as floating transient or continuous contacts
- 1 relay with 1 NO and 1 NC for all faults
Device data | |
Article number | 2500971 |
Product designation | IKI-20B1 Short-circuit / earth short-circuit indicator | battery buffered | 1 relay output changeover contact |
Controls and display | |
Red LED (1) | Collective display |
Buffer of power supply | Lithium battery |
Dimensions and installation instructions | |
Case height x width x depth | 48 x 96 x 80 mm |
Cutout height x width | 45 x 92 mm |
Norm cutout dimensions | DIN 43700 |
Installation type | Panel mounting |
Operating conditions | |
Operating temperature | -25°C ... 75°C |
Storage temperature | -30°C ... 75°C |
Protection class | IP40 |
Fault Detection | |
Short circuit detection I>> | ✓ |
Threshold current short-circuit detection I>> [A] | 100, 200, 300, 400, 600, 800, 1000, 2000 |
Threshold time short-circuit detection I>> [ms] | 60, 80, 150, 200 |
Earth short-circuit detection Ie>> | ✓ |
Threshold current earth short-circuit detection Ie>> [A] | 40, 80, 100, 150 |
Threshold time earth short-circuit detection Ie>> [ms] | 60, 80, 150, 200 |
Fault reset | Auto, Manually on the device, After 2h, 4h, External potential-free normally open contact |
Interfaces and communication | |
Slave test | ✓ |
Switching capacity relay | Umax = 220 Vdc, 250 Vac Imax = 0,1 A |
Relay outputs | 1x (Changeover) |
Potential-free contacts | 1 relay with 1 NO contact and 1 NC contact for all fault messages |
Power supply | |
Auxiliary power supply | Powered by CTs |
Insulation voltage | 1 kV / 1 min |
Battery | Lithium battery: 3,6 V; LS14500; Kries-item.no.: 3500934 |
Battery life | Greater than 17 years with current sensors not connected; for operation with current sensors and operating currents greater than 5A: at least 30 years |
CT-supplied | ✓ |
Notes on transformer supply | With a primary current of >=5A through a split-core CT at the inputs L1, L2 or L3, the energy supply is made from the sensors. At primary currents <4A, power is supplied from the energy buffer. With primary currents 1A <I <5A, a mixed supply takes place. |