IKI-Overhead R2

IKI-Overhead R2

Fault indicator for overhead line | Connection: Ring eyelet

Item number: 2501302_H001
With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus integrated... more
Product information "IKI-Overhead R2"
With the IKI-Overhead R2, overhead lines can be easily monitored for faults and thus integrated into the overall protection concept to minimize downtime. Fault indication is provided locally via strong LEDs.

Fault detection of all typical overhead line faults

Short circuits, transients and ground faults

Ultra-bright LED display

Visibility cone 360°, visible even in bright sunlight

Easy installation using actuating rod

Integrated torque indicator shows correct installation. No additional tools required.

Reliable fault detection

Overcurrent and short-circuit via to independent current/time characteristic; short and earth (short) circuit detection; high impedance fault detection by dI/dT detection; inrush suppression; fault confirmation by monitoring for disconnection via integrated voltage sensor

Simple parameter setting by DIP switch

Response current (automatic or fixed thresholds 200 - 600 A). Reset time (2 - 8 h, manual or automatic after load current recovery). Access to DIP switches possible without tools.

Long life

due to high quality lithium battery, nanowatt technology and corrosion-free housing.

Easy installation

Torque indicator for safe mounting
.
Device data
Article number2501302_H001
Product designationIKI-Overhead-R2 Fault indicator for overhead line
Connection: Ring eyelet
Display
Display VisibilityApprox. 50-100 m in bright sunlight
approx. 500 m at night
Display flashing frequency30 per minute
Brightness display13 Candela
Dimensions and installation instructions
Connection type for insulating poleRing eyelet
Case height x width x depth250 x 104 x 145 mm
Conductor cross section20 - 490 mm²; 5 - 35 mm diameter
Operating conditions
Operating temperature-30°C ... 75°C
Storage temperature-30°C ... 80°C
Protection classIP67
Voltage levelApplicable up to 36 kV
Maximum height operation4500 m above sea level
Maximum wind force70 m/s
Fault detection
Short circuit detection I>>
Threshold current short-circuit detection I>> [A]200, 400, 600
Automatic response threshold Short circuit detection
Threshold time short-circuit detection I>> [ms]80, 150
Threshold time short-circuit detection (I>>) adjustable via DIP [ms]80, 150
Waiting time after current switch-off (short-circuit detection) [ms]200
Earth short-circuit detection Ie>>
Reset setting2, 4, 8 h
ResetTime, manually by actuating rod, automatically after load current return > 3 A
Power supply
BatteryLithium battery
Battery lifeApprox. 15 years
Total flashing duration (Battery life)2880 hours (120 days)