IKI-55 M
Feeder Control Units for distribution substations, with ModbusRTU (Slave)
Item number: 2502400_H001
The IKI-55 Feeder Control Unit can be used in load switchgear for directional fault detection, load flow measurement, and control of load and ground switches. Likewise, a number of automation and monitoring functions are available with the IKI-55.
The IKI-55 is network-capable in its basic version and can communicate with the control station and other remote stations via various communication protocols. It can also be used as a Modbus master. The IKI-55 M is a Modbus-only variant.
The IKI-55 is designed for the connection of small-signal current transformers according to IEC 61869-10 as well as small-signal voltage transformers according to IEC 61869-11. In conjunction with a sensor adapter, conventional conversion transformers for current measurement as well as capacitive and precision dividers can be connected.
Fault detection
- Directional short-circuit detection
- Directional ground short-circuit detection
- Directional ground fault detection with static and transient fault detection
- Ground fault detection via pulse locating
- Suitable for all neutral point treatments
- No summing transformer required
- Fault recording with export as Comtrade file
Early fault detection
- Fetection of transient faults (Intermittent ground faults)
- In conjunction with a CAPDIS- S2_55 (R5): Detection of partial discharges and their frequency and trend
Load flow measurement
- Voltages, currents, powers, frequencies, cos phi
- Momentary and average values
- Cross calibration (With additional adapter)
- Phase comparison function for voltages (With additional adapter)
Comprehensive control and monitoring functions
- Control of motor controllers for switching load and ground switches
- Free programmable logic functions
- Automatic Transfer Switch (ATS)
- Limit value monitoring
Simple operation of the unit
- Additional LEDs to indicate the fault direction
- Self-explanatory operation via direction keys
Extended safety features
- User roles safety concept, password protected
- USB interface deactivable
Communication protocol
- ModbusRTU-Slave
Comparison of products
| IKI-55 M 2502400_H001 | IKI-55 2502400_H003 | |
| Level of digitalisation | 2 | 2 |
| Directional short-circuit detection I>> | ✓ | ✓ |
| Directional earth short-circuit detection Ie>> | ✓ | ✓ |
| Earth fault transient detection | ✓ | ✓ |
| Pulsation detection | ✓ | ✓ |
| Directional static earth fault detection Ie>; | ✓ | ✓ |
| Slave test | ✓ | ✓ |
| Modbus-RTU | ✓ | ✓ |
| Modbus RTU Master | - | ✓ |
| Modbus-RTU Slave | ✓ | ✓ |
| IEC 60870-5-104 Slave | - | ✓ |
| MQTT | - | ✓ |
| REST API | - | ✓ |
| LAN connection | - | ✓ |
| Encryption of communication (LAN) | TLS | |
| CT-supplied | - | - |
| Auxiliary power supply | 24 VDC/AC +/-20% | 24 VDC/AC +/-20% |
| USB interface | Mini-USB | Mini-USB |
| PT100 input for temperature compensation of sensors | - | - |
| Digital Inputs | 6 | 6 |
| Digital Outputs | 6 | 6 |
| Digital IOs configurable | Yes | Yes |
| Switching functions feeder control unit | Switching of up to two load switches 1.5-pole switching | Switching of up to two load switches 1.5-pole switching |
| Digital outputs for 1.5 pole switching | 2 | 2 |
| Voltage inputs | 1 (With additional adapter 2: 2x LRM/CAPDIS or 1x LRM/CADPIS + 1x precision 3.25V) | 1 (With additional adapter 2: 2x LRM/CAPDIS or 1x LRM/CADPIS + 1x precision 3.25V) |
| Voltage measurement | ✓ | ✓ |
| Precision voltage measurement | Yes | Yes |
| Current measurement | ✓ | ✓ |
| Logic functions programmable | A total of 32 logic rules can be programmed. | A total of 32 logic rules can be programmed. |
| Balanced core CT optional | - | - |
| Stromwandlerliste für Vergleichstabelle | IKI-LUM_d92 Split-Core Transducer with cable tie (set) | Ø 92mm (2512106_H001) IKI-LUM_d92 Split-Core Transducer for C-Cone-Bushings (set) | Ø 92mm (2512106_H003) IKI-LUM_d92 Split-Core Transducer for SIEMENS-Bushings (set) | Ø 92mm (2512106_H004) | IKI-LUM_d92 Split-Core Transducer with cable tie (set) | Ø 92mm (2512106_H001) IKI-LUM_d92 Split-Core Transducer for C-Cone-Bushings (set) | Ø 92mm (2512106_H003) IKI-LUM_d92 Split-Core Transducer for SIEMENS-Bushings (set) | Ø 92mm (2512106_H004) |
| TE trend monitoring |
|
|
| Device data | |
| Article number | 2502400_H001 |
| Quantity unit | Piece |
| Product designation | Grid Controller IKI-55 M | ModbusRTU |
| Number of feeders | 1 |
| Parameterization software | KriesConfig |
| Configuration | Via HMI and display (limited), Via software Kries-Config (download at kries.com) |
| Firmware update | Via USB interface |
| Operating elements and display | |
| Front display | LC-Display and LEDs |
| Direction keys | 1 - 4 for navigation in menu |
| Red LED (1) | Error event detected |
| Yellow LED (2) | Device warnings |
| Dreen LED (3) | Status message device state |
| Yellow LED (4) | Fault detected in the direction of the busbar |
| Red LED (5) | Error event detected in the direction of the cable |
| Dimensions and installation instructions | |
| Case height x width x depth | 48 x 96 x 110 mm |
| Cutout height x width | 45 x 92 mm |
| Norm cutout dimensions | DIN IEC 61554:2002-08 |
| Installation type | Panel mounting |
| Operating conditions | |
| Operating temperature | -40°C ... 70°C |
| Storage temperature | -40°C ... 80°C |
| Protection class front side | IP54 |
| Protection class | IP40 / Front IP54 |
| System frequency | 50 Hz / 60 Hz (selectable) |
| Fault detection and failure forecast | |
| Fault detection | Individually selectable, any combinations possible |
| Star point types | Short-term low-ohmic terminated neutral, Low-ohmic terminated neutral, Inductive terminated neutral, Isolated neutral |
| Short circuit detection I>> | ✓ |
| Directional short-circuit detection I>> | ✓ |
| Threshold current short-circuit detection I>> | 50 A – 1,000 A |
| Threshold time short-circuit detection I>> | 40 ms – 5 s |
| Earth short-circuit detection Ie>> | ✓ |
| Directional earth short-circuit detection Ie>> | ✓ |
| Threshold current earth short-circuit detection Ie>> | 10 A – 1,000 A |
| Threshold time earth short-circuit detection Ie>> | 40 ms – 5 s |
| Directional static earth fault detection Ie>; | ✓ |
| Threshold current static earth fault detection Ie> | 2 A – 30 A |
| Threshold time static earth fault detection Ie> | 200 ms – 2 s |
| Directional transient earth fault detection Ie> | ✓ |
| Threshold current transient earth fault detection 3I0 | 1 A – 1,000 A |
| Threshold voltage transient earth fault detection 3U0 | 0.1 kV – 100 kV |
| Earth fault detection via pulse locating | ✓ |
| Pulse length of pulse locating | symmetrical / asymmetrical |
| Transient fault detection IIe> | ✓ |
| TE trend monitoring |
|
| Fault reset | Auto, Manually on the device, After time (1 h ... 8 h, configurable) |
| Reset setting | Time: 1 - 1 h; manual, auto |
| Event log | 20 events |
| Fault recorder | ✓ |
| Fault record - formats | Comtrade |
| Fault record - number | 20 |
| Fault record - recording duration | 2,5 s at 50 Hz | 2,09 s at 60 Hz |
| Fault record - Frequency | 6,4 kHz at 50 Hz | 7,68kHz at 60 Hz |
| Fault record - Pretrigger | 0,31 s at 50 Hz | 0,258 s at 60 Hz |
| Earth fault transient detection | ✓ |
| Directional earth short-circuit detection | ✓ |
| Interfaces and transmission protocols | |
| USB interface | Mini-USB |
| Transmission protocols | Modbus-RTU (Slave) |
| Modbus-RTU | ✓ |
| Modbus RTU Master | - |
| Modbus-RTU Slave | ✓ |
| Modbus transmission rates [kBd] | 9600, 19200, 38400, 57600, 115200 |
| MQTT | - |
| REST API | - |
| IEC 60870-5-104 Slave | - |
| LAN connection | - |
| Slave test | ✓ |
| Digital Inputs | 6 |
| Digital inputs - connections | Push-In, Connection of solid and stranded conductors: 0.08 to 0.5 mm² | Connection of stranded conductors with ferrule: 0.25 to 0.34 mm² |
| Digital inputs - switching thresholds | ON > 19 VDC / OFF < 10 VDC |
| Digital inputs - voltage ranges | 24 DC to 60 VDC |
| Digital inputs - current consumption | Max. 6 mA |
| Digital Outputs | 6 |
| Digital outputs for 1.5 pole switching | 2 |
| Digital outputs - connections | Push-In, Connection of solid and stranded conductors: 0.08 to 0.5 mm² | Connection of stranded conductors with ferrule: 0.25 to 0.34 mm² |
| Digital outputs - variants | Floating |
| Digital outputs - switching capacity | 1 A at 30 VDC |
| Digital outputs - dielectric strength | Max. 80V |
| Digital IOs configurable | Yes |
| Switching functions feeder control unit | Switching of up to two load switches 1.5-pole switching |
| Voltage input Input impedance | 2 MOhm, 50 pF |
| Voltage input Input range | 0,4 V – 4,1 V |
| Voltage input measurement accuracy | 1% |
| Voltage input transformation ratio | 10000:1 (settable) |
| Voltage input standard | IEC 61869-11 |
| Current input Version | Rogowski current sensor |
| Current input Input impedance | 10 MOhm, 50 pF |
| Current input Measuring range | 0,1 A up to 2000 A |
| Current input Measuring accuracy | 1%, +- 0.5 A |
| Current input Ratio | 50 A / 22,5 mV (50Hz) (settable) |
| Current input standard | IEC 61869-10 |
| PT100 input for temperature compensation of sensors | - |
| Voltage inputs | 1 (With additional adapter 2: 2x LRM/CAPDIS or 1x LRM/CADPIS + 1x precision 3.25V) |
| Measurement values and functions | |
| Voltage measurement | ✓ |
| Phase-to-ground voltages | ✓ |
| Phase to phase voltages | ✓ |
| Precision voltage measurement | Yes |
| Current measurement | ✓ |
| Active power | ✓ |
| Reactive power | ✓ |
| Apparent power | ✓ |
| Rotary field detection | ✓ |
| Frequency measurement | ✓ |
| Limit value monitoring | Parameterizable |
| Logic functions programmable | A total of 32 logic rules can be programmed. |
| Power supply | |
| Auxiliary power supply | 24 VDC/AC +/-20% |
| Power input - power consumption | 0.5 A |
| Power supply input - connections | Connection of solid and stranded conductors: 0.2 to 2.5 mm2 / Connection of stranded conductors with ferrule: 0.25 to 1.5 mm2 / Connection of stranded conductors with ferrule without plastic collar: up to 2.5 mm2 |
| CT-supplied | - |