This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Track device being used
IKI-35_24V
Transformer monitor, Protection Relay according to EN 60255, LCD and USB, 24V release
Item number: 2503290_H003
Item number: 2503290_H003
The IKI-35 is a compact overcurrent protection relay and is suitable as overload, short-circuit... more
Product information "IKI-35_24V"
The IKI-35 is a compact overcurrent protection relay and is suitable as overload, short-circuit and earth short-circuit protection in combination with circuit breakers or power isolators, as well as overload protection in combination with load disconnectors and HRC fuses. The IKI-35 can be parameterized via menu or software.
- Application as transformer protection
- Availabe with wide range converters
- Overcurrent, short-circuit, and earth fault stage
- Intuitive operation thanks to menu navigation
- Inrush suppression
- Event memory
- Earth fault protection by balance current transformer or calculation from the phase current transformers possible
- IDMT I>, four characteristic curves (ANSI 51)
- 2 short-circuit levels I>>, I>>> (ANSI 50)
- External quick-trigger
- Earth fault level DMT or IDMT Ie> (ANSI 51N or 51G)
- Instant earth fault level Ie>> (ANSI 50N or 50G)
- Low-energy triger,0.02 Ws, without external power supply
- Low-energy trigger,24 V/0.1 Ws, without external power supply
- Standard trigger coil (with additional - external capacitor storage PSU)
Event memory for 20 events
Availabe for download with mini USB cable via software (PC)
due to transformer power supply Internal battery life > 15 years without transformer current
Current transformer supplied protection relay
- Application as transformer protection
- Availabe with wide range converters
- Overcurrent, short-circuit, and earth fault stage
- Intuitive operation thanks to menu navigation
- Inrush suppression
- Event memory
- Earth fault protection by balance current transformer or calculation from the phase current transformers possible
Trigger characteristics
- DMT I> (ANSI 51)- IDMT I>, four characteristic curves (ANSI 51)
- 2 short-circuit levels I>>, I>>> (ANSI 50)
- External quick-trigger
- Earth fault level DMT or IDMT Ie> (ANSI 51N or 51G)
- Instant earth fault level Ie>> (ANSI 50N or 50G)
Magnetic trigger selectable
- Low-energy triger,0.02 Ws, without external power supply
- Low-energy trigger,24 V/0.1 Ws, without external power supply
- Standard trigger coil (with additional - external capacitor storage PSU)
Self-test function
Event memory for 20 events
Availabe for download with mini USB cable via software (PC) Low-maintenance
due to transformer power supply Internal battery life > 15 years without transformer current
Device data | |
Article number | 2503290_H003 |
Product designation | IKI-35 Transformer Monitor | Protection Relay according to EN 60255 | LCD and USB | 24V release |
Standard | IEC 60255-1 |
Dimensions and mounting instructions | |
Case height x width x depth | 48 x 96 x 80 mm |
Cutout height x width | 45 x 92 mm |
Norm cutout dimensions | DIN 43700 |
Installation type | Panel mounting |
Operating conditions | |
Operating temperature | -40°C ... 70°C |
Storage temperature | -40°C ... 80°C |
Protection class | IP40, IP54 |
Rated frequency | 50 Hz, 60 Hz |
Technical Data Protection Functions | |
Reset | settable 2 h / 4 h / 8 h, autom. after load current restoring, manual |
Setting / nominal current setting range | 10 .. 250 A, 100 .. 400 A |
Protection levels | ANSI 50, ANSI 50N, ANSI 51, ANSI 51N |
Intrinsic time | 43 ms |
Threshold value I>>/In | settable 2 .. 32 or deactivated |
Delay time I>> | Settable 0 .. 2 s |
Threshold value UMZ I> | settable 1.1 .. 3 |
Delay time UMZ | Settable 0,3 .. 300 s |
Protection characteristics IDMT | IEC extremely invers, IEC long time invers, IEC normal invers, IEC very invers |
Start value I>/In | settable 1,1 .. 3 |
Displacement factor v I> | Settable 0,05 .. 10 s |
Threshold value Ie>> | settable 0,1 .. 2 or deactivated |
Delay time tIe>> | Settable 0 .. 2 s |
Threshold value UMZ Ie> | settable 0,1 .. 2 |
Delay time UMZ Ie> | Settable 0 .. 5 s |
Start value Ie>/In | settable 0,1 .. 2 |
Displacement factor v Ie> | Settable 0,05 .. 10 s |
Interfaces and communication | |
Remote signalling | 2x, settable NO / NC, settable logic: I> + Ie>; I>; Ie>; Trip |
Power supply | |
Power supply | 24 - 230 V AC/DC +- 10%; Power input < 1 Watt |
Battery type | Lithium battery |
CT-supplied | ✓ |
IKI-LUM d92
CT for bushings, directional, for measured value acquisition, for C-cone, set
Price on request
IKI-LUM d92
CT for bushings, directional, for measured value acquisition, for Siemens switchgears, set
Price on request