This website uses cookies, which are necessary for the technical operation of the website and are always set. Other cookies, which increase the comfort when using this website, are used for direct advertising or to facilitate interaction with other websites and social networks, are only set with your consent.
Configuration
Technically required
These cookies are necessary for the basic functions of the shop.
"Allow all cookies" cookie
"Decline all cookies" cookie
CSRF token
Cookie preferences
Currency change
Customer recognition
Customer-specific caching
Individual prices
Selected shop
Session
Comfort functions
These cookies are used to make the shopping experience even more appealing, for example for the recognition of the visitor.
Note
Statistics & Tracking
Affiliate program
Google Analytics
Track device being used

IKI-50_1F R2
Universal Feeder Control Units, single-field monitoring, pulsation method, wiper mode, resistive and capacitive voltage measurement
Item number: 2502352
Item number: 2502352
The universal Feeder Control Unit IKI-50_1F R2 is the appropriate solution for intelligent... more
Product information "IKI-50_1F R2"
The universal Feeder Control Unit IKI-50_1F R2 is the appropriate solution for intelligent distribution network stations and offers distribution network operators a high level of transparency and cost-effectiveness. The IKI-50_1F R2 includes all algorithms for selective fault detection. It is suitable for all neutral point treatments. Switching commands for load switch control can be fed to the IKI-50_1F R2 via communication bus and executed field-related with 1.5-pole switching safety.
Fault detection
- directional short-circuit detection
- directional earth fault detection, directional static earth fault detection (wattmetric method), directional transient earth fault detection (wiper method), earth fault detection via pulse locating
- suitable for all neutral point treatments
- no summing transformer required
fault early detection
- fault early detection by detection of transient disturbances
- partial discharge trend detection together with CAPDIS-S2_55 (R5)
load flow measurement
- voltages, Currents, powers, frequencies, cos-phi, . ..
- Momentary and average values
- Limit value monitoring
Remote control and network automation
- selective control of up to two motors
- extensive logic functions freely programmable with PC software KriesConfig
IKI- 50_F1 R2 is maintenance-free
- no battery
- unlimited data retention
- error indication in case of power failure over 6 hours
precise voltage measurement with precision dividers
- optional voltage measurement with precision dividers, z. E.g. resistive sensors
- two voltage inputs: 1x capacitive, 1x resistive
- patented method for voltage calibration via a reference measurement from another feeder
Device data | |
Article number | 2502352 |
Product designation | IKI-50_1F R2 |
Number of feeders | 1 |
Firmware | Version V54.0.0 or higher |
Parameterization software | KriesConfig |
Configuration | Via software Kries-Config (download at kries.com), Via HMI and display (limited) |
Operating elements and display | |
Front display | LC-Display and LEDs |
Direction keys | Operation via four direction keys |
Red LED (1) | Error event detected | internal energy storage empty |
Yellow LED (2) | Slave Test | Primary Test | Device Warnings |
Dreen LED (3) | Status message device state |
Dimensions and installation instructions | |
Case height x width x depth | 49 x 96 x 108 mm |
Cutout height x width | 45 x 92 mm |
Norm cutout dimensions | DIN IEC 61554:2002-08 |
Installation type | Panel mounting |
Sheet thickness | 1.5 ... 2.5 mm |
Operating conditions | |
Operating temperature | -25°C ... 55°C |
Storage temperature | -25°C ... 70°C |
Humidity | max. 95 % relative Feuchte bei 40° C |
Protection class | IP54 (Front) |
Fault detection and failure forecast | |
Fault detection | Individually selectable, any combinations possible |
Star point types | Short-term low-ohmic terminated neutral, Low-ohmic terminated neutral, Inductive terminated neutral, Isolated neutral |
Directional short-circuit detection I>> | ✓ |
Threshold current short-circuit detection I>> | 100 A ... 1,000 A (adjustable in steps) |
Threshold time short-circuit detection I>> | 40 ms ... 1,600 ms (adjustable in steps) |
Directional earth short-circuit detection Ie>> | ✓ |
Threshold current earth short-circuit detection Ie>> | 40 A ... 1,000 A (adjustable in steps) |
Threshold time earth short-circuit detection Ie>> | 40 ms ... 1,600 ms (adjustable in steps) |
Directional static earth fault detection Ie>; | ✓ |
Threshold current static earth fault detection Ie> | 2 A ... 30 A (adjustable in steps) |
Directional transient earth fault detection Ie> | ✓ |
Threshold current transient earth fault detection 3I0 | 1 A ... 1,000 A (freely adjustable) |
Threshold voltage transient earth fault detection 3U0 | 1 kV ... 300 kV (freely adjustable) |
Earth fault detection via pulse locating | ✓ |
Pulse length of pulse locating | symmetrical / asymmetrical |
Transient fault detection IIe> | ✓ |
TE trend monitoring |
|
Fault reset | Auto, Manually on the device, After time (1 h ... 8 h, configurable) |
Event log | The last 20 fault events are stored with event number, date, time, name of the triggering fault detection, fault direction, phase and fault current value. |
Interfaces and communication | |
USB interface | Mini-USB |
Modbus-RTU Slave | ✓ |
Modbus transmission rates [kBd] | 9600, 19200, 38400, 57600, 115200 |
Digital Inputs | 6 |
Potential-free digital inputs | 4 |
Digital Outputs | 6 |
Digital outputs for 1.5 pole switching | 2 |
Connection cable cross section | Max. 2,5 mm |
Switching capacity relay | AC: max. 62,5 VA max. 2A; max. 250 VAC DC: max. 2A @ 40 VDC |
Measurement values and functions | |
Voltage measurement | ✓ |
Measuring range voltage | Capacitive (Input F1), Precision divider with an output signal of 3.25 V/sqrt(3) in nominal operation (input UF2) |
Phase-to-ground voltages | ✓ |
Phase to phase voltages | ✓ |
Measuring range voltage | 0.02 kV ... 92 kV | Start of voltage measuring range: 2% of Un |
Accuracy voltage measurement | Input UF1 (capacitive): 3 % of measurement value after on-site calibration Input UF2 (resistive): 0.5 % of measurement value |
Current measurement | ✓ |
Measuring range current | 0.5 A ... 1,158 A (with current transformer IKI-LUM) |
Zero-sequence current | ✓ |
Accuracy current measurement | 3 % of measurement value, optionally 1% of measurement value |
Conductor currents | ✓ |
Active power | ✓ |
Reactive power | ✓ |
Apparent power | ✓ |
Rotary field detection | ✓ |
Frequency measurement | ✓ |
Mean value determination | ✓ |
Min-max value determination | ✓ |
Phase position | ✓ |
Phase shift cos-phi | ✓ |
Limit value monitoring | Voltage, current, frequency, reactive power and voltage |
Logic functions | A total of 32 logic rules can be programmed. |
Switching functions | Switching of up to two load switches 1.5-pole switching |
Power supply | |
Auxiliary power supply | 24...230 VAC/DC (jeweils 15 %) |
Power consumption | 2 W |
Insulation voltage | 2 kV, 1 min |
Display buffer for fault indication | Unlimited data retention (independent of auxiliary power and buffer power); Error display after power failure (depending on adjustable follow-up time):
|